Heat Loss & Heating BTU Calculator

The heating load of every room — fabric and air losses, and the radiator it needs.

Free preview, no sign-upIncluded in your pass Pro tool Pro pass: ₹179 / $5.99 for 30 days On this device: nothing is sent
+3 +1 more details No uploadWorks offline once opened Construction

Free preview: the design heat loss of the whole home in full, with the first rows of the room table (up to 3); every other figure is hidden. Locked until you unlock it: download and copy.

Pro pass ₹179 for 30 days or ₹79 for 1 week, one‑time. Pro pass $5.99 for 30 days or $2.99 for 1 week, one‑time. How to unlock

Try before you buy.

  • Free preview: the design heat loss of the whole home in full, with the first rows of the room table (up to 3); every other figure is hidden.
  • Locked until you unlock it: download and copy.
  • Unlock: Pro pass, ₹179 for 30 days or ₹79 for 1 week, a one-time payment that never renews. Unlock: Pro pass, $5.99 for 30 days or $2.99 for 1 week, a one-time payment that never renews.

Ways to unlock shows how to get the full result.

See passes (opens in a new tab)

Printing this result is locked in the free preview.

Design conditions

°C
A cold day for your area, not the record low.
°C
For floors on the ground (MIS 3005-D). Empty: the design temperature is used.
W/m²K
Added to each outer element’s U. SAP uses 0.20 when the details are unknown; 0 leaves it out.
%
Optional, e.g. for warming up after a setback.

Air leakage

m/s
SAP scales the leakage by the month’s average wind ÷ 4 m/s, so 4 m/s (9 mph) leaves it as it is; its UK average for January is 5.1 m/s.
%
Chimneys, flues, fans and vents

Ground floor U-value (ISO 13370)
m²
m
Outside walls around the floor, not walls to heated neighbours.
m
m²K/W
0 for none; 50 mm of EPS is about 1.4 m²K/W.

Heated rooms

    Radiators

    °C
    About 75 for a boiler; 35–55 for a heat pump.
    °C
    From the radiator’s EN 442 data.
    Design heat loss, whole home —

      Heat loss and radiator size by room

      Your rooms are kept in this browser only. Reset clears them.

      Results are estimates from the formulas shown, not a professional design or certification. Have a qualified engineer verify anything safety-critical (structures, electrical installations, gas or pressure systems).

      About the Heat Loss & Heating BTU Calculator

      Work out how much heat each room loses on a cold day — and so how big its radiator, heater or the whole heating system must be. For every wall, window, door, roof and floor the calculator multiplies its U-value by its area and by the temperature difference across it; it adds the heat carried away by air leaking in and out (0.33 × air changes per hour × volume × ΔT), and shows each room in watts and BTU/h and the house in total.

      Room temperatures start from the CIBSE values that the UK’s MCS heat pump standard uses, cold-day design temperatures for 14 UK sites are built in (or type your own), the air leakage can be estimated the way SAP 10.2 does, and a ground floor’s U-value can be worked out by ISO 13370. Radiators are sized for the water temperature you run — a 75 °C boiler or a 45 °C heat pump. An estimate for choosing heating — not a professional design.

      Without a pass, the free preview shows the design heat loss of the whole home in full, with the first rows of the room table; the complete result, Copy result and the CSV come with a Pro pass.

      How to use it

      1. Set the outdoor design temperature — pick a UK site, or type your local cold-day figure — and, for floors on the ground, the annual average outdoor temperature.
      2. Choose how to count air leakage: estimate it from the house (storeys, construction, draught-proofing, chimneys and fans), type an air-test result, or give each room its own air changes per hour.
      3. Add each heated room: its type (which sets the temperature), length, width and height, then its walls, windows, doors, roof or ceiling and floor with their areas and U-values. Put each window in its wall so its area is taken off.
      4. Set the radiator water temperatures: about 75/65 °C for a boiler, 45/40 °C or lower for a heat pump.
      5. Read each room’s loss in watts and BTU/h and the catalogue output (ΔT 50) of the radiator it needs. Copy result or Download CSV for your installer — with a pass, or after unlocking this result; your rooms stay in this browser.

      Examples

      Living room, 5 × 4 × 2.4 m, 21 °C inside, −3 °C outside
      Input
      12 m² brick wall (U 2.11) with a 1.5 m² double-glazed window (U 2.8); 20 m² ground floor (U 0.70) to an annual average of 10 °C; room above heated; 1 air change an hour
      Result
      Wall 10.5 × 2.11 × 24 = 532 W, window 101 W, floor 20 × 0.70 × 11 = 154 W, air 0.33 × 1 × 48 × 24 = 380 W → 1,167 W (3,981 Btu/h).
      A radiator for that room
      Result
      With a boiler at 75/65 °C the water averages 70 °C, 49 K above the 21 °C room, so a radiator gives 97% of its ΔT 50 rating: about 1,200 W at ΔT 50 (1,167 ÷ 0.974). With a heat pump at 45/40 °C (ΔT 21.5 K, n = 1.3) it gives only 33% of its rating, so it needs a catalogue output of about 3,500 W.
      Air leakage estimated the SAP way
      Input
      Two-storey brick home, no draught lobby, all windows draught-proofed, no chimney
      Result
      0.1 + 0.35 + 0.05 + 0.05 = 0.55 air changes an hour, 0.65 once natural ventilation is allowed for (0.5 + 0.5 × 0.55²). An open chimney in a 250 m³ home adds 80 m³/h = 0.32 more.

      Common uses

      • Size a radiator, a panel heater or an oil-filled heater for one cold room.
      • Find the whole-house heat loss before choosing a boiler or a heat pump.
      • Check whether existing radiators are big enough to run at heat-pump temperatures.
      • See what new windows, loft insulation or draught-proofing would save in peak heating power.

      The calculation

      • Fabric loss of each element: Φ = U × A × (θ_room − θ_beyond), in watts. Walls are entered with their full area; the windows and doors in them are taken off.
      • What is beyond: outside air at the design temperature; for a solid floor on the ground, the annual average outdoor temperature (MCS MIS 3005-D, after MGD 007); a suspended floor uses the outdoor design temperature; an unheated garage or a neighbour’s home has its own temperature, which you enter.
      • Ventilation and infiltration: Φ = 0.33 × n × V × (θ_room − θ_outside), where n is air changes per hour and V the room volume in m³; 0.33 is air’s heat capacity, 1.2 kg/m³ × 1,005 J/kg·K ÷ 3,600 s.
      • Thermal bridging (optional): an allowance y added to the U-value of every element facing outside, the ground or unheated space — SAP 10.2 uses 0.20 W/m²K when the junction details are unknown.
      • BTU/h = watts × 3.412. The total is the heat the heating must deliver on the design day; a margin can be added for reheating after setbacks.

      Temperatures

      Inside (CIBSE, as MIS 3005-D Table 1 lists them): living, dining and bedsitting rooms 21 °C, bedrooms, halls and landings, kitchens and toilets 18 °C, bathrooms 22 °C. CIBSE’s Domestic Heating Design Guide uses 21 °C throughout newer, well-insulated homes, with 22 °C in bathrooms — tick “newer, well-insulated home”.

      Outside: the design temperature is a cold-day value that is exceeded most of the time, not the record low. For the UK the calculator has CIBSE Guide A Table 2.5 for 14 sites at the 99.6% and 99% levels (London Heathrow −3.0 / −1.7 °C, Glasgow −5.6 / −3.5 °C), lowered by 0.6 °C for each whole 100 m your home stands above the site. Elsewhere use your national value — for example the ASHRAE 99.6% heating dry-bulb for North America, or the national annex to EN 12831 in Europe.

      Air leakage (SAP 10.2)

      Leaky homes lose much of their heat through air. The SAP 10.2 worksheet adds: 80 m³/h for each open chimney, 20 for an open flue or a blocked chimney, 10 for a chimney with a closed fire, 20 for a solid-fuel boiler flue, 35 for another heater’s flue, 10 for each intermittent extract fan or passive vent and 40 for a flueless gas fire, divided by the home’s volume; then 0.1 for each storey above the first, 0.35 for masonry or 0.25 for timber or steel frame, 0.2 for an unsealed suspended timber floor (0.1 sealed), 0.05 without a draught lobby, and 0.25 − 0.2 × the share of windows and doors draught-proofed. An air-pressure test result (m³/h per m² at 50 Pa) divided by 20 replaces the construction terms. Each sheltered side takes off 7.5%; SAP then scales the rate by the month’s average wind speed ÷ 4 m/s (its UK average for January is 5.1 m/s), so enter the wind of your coldest month — 4 m/s leaves the rate as it is. Below one air change an hour natural ventilation gives 0.5 + 0.5 × n². CIBSE’s guide sets 0.5 air changes an hour as the minimum for a room with outside walls.

      Ground floors and radiators

      Ground floor U-value (ISO 13370, a slab on the ground): B′ = floor area ÷ (half the exposed perimeter), d_t = wall thickness + λ_ground × (0.17 + R_floor + 0.04); U = 2λ ÷ (πB′ + d_t) × ln(πB′ ÷ d_t + 1), or λ ÷ (0.457B′ + d_t) for a well-insulated floor. Clay or silt has λ = 1.5, sand or gravel 2.0 and rock 3.5 W/m·K. An uninsulated 100 m² floor with 40 m of outside wall on sand is about 0.76 W/m²K.

      Radiators are sold by their output at ΔT 50 — water averaging 70 °C (75 °C in, 65 °C out) in a 20 °C room (EN 442). At other temperatures the output scales with (ΔT ÷ 50)ⁿ, where n comes from the radiator’s test data — the calculator starts at 1.3; use your radiator’s own figure. A heat pump running at 45/40 °C in a 21 °C room has ΔT 21.5, so a radiator gives about a third of its catalogue output — which is why heat pump homes often need bigger radiators.

      Sources

      Limitations

      • An estimate for choosing heating — not a professional design. MCS-certified heat pump installations in the UK are designed from a full room-by-room BS EN 12831 calculation (MIS 3005-D); other countries have their own rules.
      • The result is the peak heating power on the design day, not the energy used over a winter.
      • U-values must be right for the result to be: ask for the values of your windows and insulation, or work a wall out with the R-value calculator. Ceilings to a cold loft are treated as if the loft were outside air.
      • Air leakage is an estimate; real homes vary widely, and an air-pressure test is the only way to know.
      • It does not include heat from people, appliances or the sun, which help in milder weather, or extra heat for rooms heated only some of the time.

      Privacy

      On this device: nothing is sent

      Everything happens in your browser. What you enter or open here is not uploaded or stored by MySmartCoPilot.

      Frequently asked questions

      What do I get without a pass?

      Without a pass, Heat Loss & Heating BTU Calculator shows the design heat loss of the whole home in full, with the first rows of the room table (up to 3); every other figure is hidden. Until you unlock it, the result can’t be downloaded or copied. A Pro, Premium or Ultimate pass, a one-time payment that never renews, unlocks the full result. The pricing page lists the passes and their prices.

      How do I calculate the heat loss of a room?

      Add up U × area × temperature difference for every wall, window, door, roof and floor, then add 0.33 × air changes per hour × room volume × temperature difference for the air. A 5 × 4 × 2.4 m living room at 21 °C with −3 °C outside, one brick outside wall with a window, a ground floor and a heated room above loses about 1,170 W.

      How many watts do I need to heat a room?

      Exactly its heat loss on the design day — it depends on insulation, windows and the climate, not on floor area alone. Rules of thumb in watts per square metre can be far out; the calculator works it out from the room itself and shows W/m² as a check.

      How do I convert watts to BTU/h?

      Multiply by 3.412: 1,000 W is 3,412 Btu/h, and 1 kW of radiator output is 3,412 Btu/h. To go back, divide Btu/h by 3.412.

      What size radiator do I need for a heat pump?

      Divide the room’s heat loss by the radiator’s output factor at your water temperature. At 45/40 °C in a 21 °C room a radiator gives about 33% of its ΔT 50 rating (n = 1.3), so a room losing 1,000 W needs radiators rated about 3,000 W at ΔT 50. At 55/45 °C the factor is about 50%.

      What outdoor temperature should I design for?

      The local design temperature — a cold value that is reached only on a few days a year — not the record low. In the UK MCS uses CIBSE Guide A Table 2.5: −3.0 °C at London Heathrow at the 99.6% level, −5.6 °C near Glasgow. Elsewhere use your national standard’s value.

      What are air changes per hour?

      How many times an hour the room’s air is replaced by outside air through leaks, vents and chimneys. Modern airtight homes may be near the 0.5 minimum CIBSE uses; older homes with open chimneys and draughty windows can be well above 1. Each air change costs 0.33 W per m³ of room for each degree.