Three-Phase Power Calculator
Balanced or per-phase loads: kW, kVA, kvar, neutral current and unbalance.
Same current in all three lines: enter the line voltage, line current and power factor.
Phase values: star (Y) and delta (Δ)
| Per phase of the load | Star (Y) | Delta (Δ) |
|---|
The line values and the power are the same for both connections. A delta-connected load has three times the impedance per phase of the star load that draws the same line current.
How it was calculated
Each phase
| Phase | I | P | Q | S | From average |
|---|
Current phasors
How it was calculated
About the Three-Phase Power Calculator
Three-phase power in two modes. Balanced takes the line-to-line voltage, line current and power factor and gives real power (kW), reactive power (kvar) and apparent power (kVA), plus the voltage, current and impedance of each phase for both star (Y) and delta (Δ) connections.
Unbalanced is for real distribution boards, where each phase carries a different load: enter the current and power factor of L1, L2 and L3 and get the totals, the neutral current as a true phasor sum, the percentage unbalance and the symmetrical components — with a phasor diagram that shows why the neutral current is what it is.
How to use it
- Choose Balanced load or Unbalanced — per phase.
- Balanced: enter the line-to-line voltage (or tap a standard one), the line current and the power factor, and say whether the current lags (motors, transformers) or leads (capacitor banks).
- Unbalanced: enter the supply voltage — line to line or line to neutral — then the current and power factor of each phase. Use 0 A for an unloaded phase.
- Read the totals and the tables. How it was calculated lists each formula with your numbers; Copy result copies a plain-text summary.
Examples
400 V line to line, 50 A, PF 0.85 lagging
P = 29.44 kW · Q = 18.25 kvar · S = 34.64 kVA · φ = 31.79° · star: 230.9 V and 50 A per phase · delta: 400 V and 28.87 A per phase
L1 20 A, L2 15 A, L3 10 A, all PF 1
P = 10.39 kW · neutral current 8.66 A (not 45 A, not 0 A) · unbalance 33.3% · I₂ ÷ I₁ = 19.2%
460, 467 and 450 (A or V)
Average 459, largest deviation 9 → 100 × 9 ÷ 459 = 1.96% unbalance
Balanced three-phase formulas
With V_L the line-to-line voltage, I_L the line current and φ the angle between phase voltage and current:
- Real power P = √3 × V_L × I_L × cos φ
- Reactive power Q = √3 × V_L × I_L × sin φ
- Apparent power S = √3 × V_L × I_L, and S² = P² + Q²
- Star (Y): phase voltage V_ph = V_L ÷ √3, phase current = I_L
- Delta (Δ): phase voltage = V_L, phase current I_ph = I_L ÷ √3
The totals are the same for both connections; only how the voltage and current are shared inside the load differs. The impedance of each phase is V_ph ÷ I_ph, so a delta load has three times the impedance per phase of a star load that draws the same line current.
Unbalanced loads and the neutral current
For a four-wire star (230/400 V) board, each phase is a single-phase load: P = V_ph × I × cos φ and Q = V_ph × I × sin φ, and the totals are the sums. The neutral carries the phasor sum of the three line currents, because the currents are 120° apart. Three equal currents at the same power factor cancel completely; 20, 15 and 10 A in phase with their voltages leave √(20² + 15² + 10² − 20×15 − 15×10 − 10×20) = √75 = 8.66 A in the neutral.
With different currents in each phase there are two ways to total the apparent power, and the calculator shows both: the arithmetic sum S₁ + S₂ + S₃, and the vector value √(P² + Q²), which is never larger. IEEE Std 1459-2010 also defines an effective apparent power that accounts for the neutral current; it is not calculated here.
Unbalance and symmetrical components
The percentage unbalance uses the NEMA MG 1 (§14.36) definition: 100 × the largest deviation from the average ÷ the average. NEMA defines it for motor supply voltages; the calculator applies the same formula to the line currents.
The symmetrical components (Fortescue, 1918) split the currents into a positive-sequence set (I₁, the balanced part), a negative-sequence set (I₂) and a zero-sequence set (I₀). The neutral current is 3 × I₀. The ratio I₂ ÷ I₁ is the stricter measure of unbalance; EN 50160 and the IEC power-quality standards use this negative-to-positive-sequence ratio for supply-voltage unbalance.
Assumptions
- The supply voltages are balanced and sinusoidal: equal in size and 120° apart.
- The phase order is L1 → L2 → L3 (positive sequence): L1 at 0°, L2 at −120°, L3 at +120°. With different power factors per phase, the reverse order would give a different neutral current.
- Unbalanced mode models a four-wire star load. A three-wire delta load has no neutral.
- Lagging current (inductive loads: motors, transformers, fluorescent ballasts) gives positive kvar; leading current (capacitor banks, some electronic supplies on light load) gives negative kvar.
Sources
- IEEE Std 1459-2010, Definitions for the Measurement of Electric Power Quantities Under Sinusoidal, Nonsinusoidal, Balanced, or Unbalanced Conditions
- IEC 60038:2009, IEC standard voltages — 230/400 V, 400/690 V, 120/208 V, 277/480 V and 347/600 V systems
- NEMA MG 1, Motors and Generators, §14.36 — definition of percentage unbalance
- C. L. Fortescue, “Method of symmetrical co-ordinates applied to the solution of polyphase networks”, Transactions of the AIEE 37 (1918)
Limitations
- Sinusoidal waveforms only. Harmonic currents from electronic loads — especially the third harmonic, which adds up in the neutral instead of cancelling — can make the real neutral current much larger than calculated here.
- Unbalanced mode assumes the supply voltages themselves are balanced; it does not take three separate phase voltages.
- Delta-connected unbalanced loads are not covered.
- The impedances in balanced mode describe the load as seen from the line terminals; they say nothing about the cable or supply impedance.
Privacy
Everything happens in your browser. What you enter or open here is not uploaded or stored by MySmartCoPilot.
Frequently asked questions
How do I calculate three-phase power?
Multiply √3 (1.732) by the line-to-line voltage, the line current and the power factor: P = 1.732 × 400 V × 50 A × 0.85 = 29.4 kW. Without the power factor you get the apparent power, 34.6 kVA.
What is the difference between star and delta?
In star (Y) each phase of the load sits between a line and the neutral point, so it sees V_L ÷ √3 (230 V on a 400 V supply) and carries the full line current. In delta (Δ) each phase sits between two lines, so it sees the full 400 V but carries only I_L ÷ √3.
How is the neutral current calculated?
By adding the three line currents as phasors, 120° apart. It is not their arithmetic sum: 20, 15 and 10 A in phase with their voltages give 8.66 A in the neutral. Enter each phase in Unbalanced mode to see it on the phasor diagram.
How much current unbalance is acceptable?
There is no single limit for load currents; the aim is to keep the phases as even as practical to reduce neutral current and losses. For motors, NEMA MG 1 looks at the supply-voltage unbalance: it derates motors when it exceeds 1% and advises against running them above 5%, because a small voltage unbalance causes a much larger current unbalance and heating.
Why does it ask whether the current lags or leads?
The power factor alone does not say which way the current is shifted. Lagging (inductive) loads draw positive reactive power and leading (capacitive) loads negative, which changes the total kvar and, with unequal phases, the neutral current.